Rated voltage
|
24 VDC
|
|
Output channels
|
32
|
|
Module current rating
|
105 mA
|
|
Maximum load voltage
|
30 VDC
|
|
Maximum channel load
|
100 mA
|
|
Maximum module load
|
3.2 A
|
|
System-to-field isolation
|
1000 VAC RMS or ±1500 VDC; external field power
|
|
Typical ON-state voltage
|
24 VDC at load current ≤0.1 A
|
|
OFF-state leakage
|
5 μA maximum
|
|
ON/OFF transition time
|
10 ms maximum
|
|
Redundant switchover output gap
|
0 ms
|
|
Operating temperature inside cabinet
|
0–60°C
|
|
Storage temperature
|
−40 to +85°C
|
|
Relative humidity
|
5–95% non-condensing through 40°C; derated to 55% above 40°C
|
|
Operating altitude
|
−300 to +3000 m
|
|
Operating temperature change
|
1°C/min maximum
|
|
Corrosion resistance
|
G3, ISA S71.04; coated 8C configuration
|
|
Output circuit
|
Sourcing, bussed outputs
|
|
Field excitation selection
|
Internal or external
|
|
Power-on insertion/removal
|
Supported
|
|
Failure-state options
|
Hold last value or shed to configured safe value
|
|
Storage temperature-change limit
|
5°C/min maximum
|
|
Operating vibration, three axes
|
5–10 Hz: 2.54 mm maximum; 10–150 Hz: 0.5 g maximum (0–peak)
|
|
Site-induced mechanical shock
|
4 g maximum at 25 ms, terminal-peak sawtooth, three axes
|
|
Per-channel output modes
|
Latched, pulsed or pulse-width modulated
|